LG AIR CONDITIONER
ERROR CODES AND DESCRIPTION
00
Text the 1, 2 or 3 digit fault code number only.
I.e. If you see fault code CH07 on your indoor unit or R/Controller, only type
7 or 07 in your text message.
01
Indoor
unit return air sensor fault. Disconnect sensor from PCB and measure
resistance. 8 kOhm at 30C and 13 kOhm at 20C if not replace sensor
1
Indoor unit return air sensor fault. Disconnect
sensor from PCB and measure resistance. 8 kOhm at 30C and 13 kOhm at 20C if not
replace sensor
02
Indoor
Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB
and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5 kOhm at 25C. If not replace sensor.
2
Indoor Pipe Sensor or Outdoor Sensor Assy fault,
Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm
at 25C, Pipe sensor = 5 kOhm at 25C. If not replace sensor.
03
Remote
controller comms error. Check wired correctly, if so check dipswitch in RC. Set
to Sg for 1 unit, or Gr for group then reset power
3
Remote controller comms error. Check wired
correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group
then reset power
04
RAC Product = Heat Sink Sensor Error, Open/Short
Cct or over 95C. Commercial Product = Condensate pump float switch risen. Check
drain pan is empty, check pump is working OK. If no pump check blue jumper plug is inserted in
socket CN Float.
4
RAC Product = Heat Sink Sensor Error, Open/Short
Cct or over 95C. Commercial Product = Condensate pump float switch risen. Check
drain pan is empty, check pump is working OK. If no pump check blue jumper plug is inserted in
socket CN Float.
05
Comms Error, check your wiring, remove external
pumps. Split/Multi - check volts from terminal N to 3 = 0 - 65 Vdc, Multi V - 4
Vdc terminals 3 and 4.
5
Comms Error, check your wiring, remove external
pumps. Split/Multi - check volts from terminal N to 3 = 0 - 65 Vdc, Multi V - 4
Vdc terminals 3 and 4
06
Indoor
unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10C
and 4 kOhm at 30C. if not replace sensor. Split = text 21
6
Indoor unit coil sensor fault. Disconnect from
PCB measure resistance. 10 kOhm at 10C and 4 kOhm at 30C. if not replace
sensor. Split = text 21
07
Multi Splits and Multi V = indoor unit is set to
run in a different mode from the master indoor unit. Set ALL indoor units to
cooling or ALL to heating to clear.
Splits = Compressor Over Current (CT2), also see Code 06.
Splits = Compressor Over Current (CT2), also see Code 06.
7
Multi
Splits and Multi V = indoor unit is set to run in a different mode from the
master indoor unit. Set ALL indoor units to cooling or ALL to heating to clear.
Splits = Compressor Over Current (CT2), also see Code 06.
Splits = Compressor Over Current (CT2), also see Code 06.
08
RAC Indoor unit BLDC Fan problem. This is caused
by the Indoor fan being locked. Check fan motor is plugged in correctly,
Electrically & Mechanically sound. Check the fan motor turns freely, check the AC Voltage supplied to the fan
motor, this will vary from 120 V ac at low speed to 170V AC at high speed. If
no Voltage is present the the PCB is faulty, if Voltage is present the fan motor
will be Faulty.
8
RAC Indoor unit BLDC Fan problem. This is caused
by the Indoor fan being locked. Check fan motor is plugged in correctly,
Electrically & Mechanically sound. Check the fan motor turns freely, check the AC Voltage supplied to the fan
motor, this will vary from 120 V ac at low speed to 170V AC at high speed. If
no Voltage is present the the PCB is faulty, if Voltage is present the fan motor
will be Faulty.
09
Split = Outdoor unit fan problem. Check Outdoor
fan motor is plugged in, Electrically & Mechanically sound, if not replace
motor, otherwise replace PCB. Multi V = Indoor unit EEPROM error - Replace the indoor unit PCB, and then make sure to
do Auto addressing and input the address of central control.
9
Split
=
Outdoor unit fan problem. Check Outdoor fan motor is plugged in,
Electrically
& Mechanically sound, if not replace motor, otherwise replace PCB.
Multi V = Indoor unit EEPROM error - Replace the indoor unit PCB, and
then make sure to
do Auto addressing and input the address of central control.
10
RAC
Product: Compressor discharge sensor fault. Disconnect from PCB measure
resistance 237 kOhm at 20°C, 168 kOhm at 30C. Multi Fdx & Multi V text 8
11
Multi V
indoor unit not connected to an outdoor unit. Check comms wiring is correct,
and check initialisation has been carried out correctly
12
RAC Product = EEPROM Sum Check Error, text 60
for help.
13
RAC
Product = PSC (Reactor) Error, text 27 for help.
14
RAC
Product = Compressor Phase Current Error
15
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
16
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
17
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
18
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
19
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
20
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
21
Inverter compressor run current high. Check
compressor windings all equal 1 to 4 Ohms, Check to earth 50 MOhm minimum,
check run current
22
Inverter compressor run current high. Check
compressor windings all equal 1 to 4 Ohms . Check to earth 50 MOhm minimum,
check run current
23
Inverter dc voltage low. Check dc voltage of
capacitors 300 Vdc for 1Ph and 600 Vdc for 3Ph. If OK change outdoor inverter
PCB
24
Splits and Multi Splits = High or low pressure
trip. Low at 1 bar High at 35 bar check pressures. Multi V = High pressure
trip.
25
Check power supply voltage to the outdoor unit
is correct (1ph ?220 Vac ±10% or 3ph ?380 Vac ±10%). If OK, check fuses, if
fuses are OK replace outdoor
main PCB
main PCB
26
Inverter compressor seized. Check compressor
windings all equal resistance 1 to 4 Ohms, check to earth 50 MOhm minimum,
check run current and Inverter
outputs
outputs
27
Inverter current irregularity. Check inverter
PCB, check reactor connections and its resistance is less than 1 ohm.
28
Inverter
dc voltage too high. Check dc voltage of capacitors 300 Vdc for 1Ph and 600 Vdc
for 3Ph. If OK change outdoor inverter PCB
29
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
30
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
31
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
32
Inverter compressor discharge temperature too
high. If over 105°C, check refrigerant charge
33
Excessive
rise of standard compressor discharge temperature. If over 105°C check
refrigerant charge
34
Excessive high pressure rise, over 35 bar at HP
sensor. Check pressures, check coils, and filters are clean check for OFN in
system pipework
35
Excessive
low pressure drop under 1 Bar at LP sensor. Check pressures, and check service
valves open
36
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
37
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
38
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
39
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
40
Inverter
ac current abnormal. Check compressor windings all equal resistance 1 to 4
Ohms, check to earth 50 MOhm minimum, check run current and inverter outputs
41
Inverter compressor discharge sensor fault.
Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C.
42
Low
pressure sensor fault. Check dc voltage between white and black cable on plug.
Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar
43
43
High
pressure sensor fault. Check dc voltage between white and black cable on plug.
Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar
44
Outdoor
unit air sensor fault. Disconnect from PCB and measure resistance. 8 kOhm at
30C and 13 kOhm at 20C. If OK replace PCB, if not replace sensor
45
Outdoor unit
coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and
4 kOhm at 30°C. If OK replace PCB, if not replace sensor
46
Outdoor unit suction sensor fault. Disconnect
from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK
replace PCB, if not replace sensor
47
Compressor discharge sensor fault. Disconnect
from PCB measure resistance. 237 kOhm at 20°C and 168 kOhm at 30°C. If OK
replace PCB, if not replace
sensor
sensor
48
Split/Multi
Split = Outdoor unit discharge and air sensor both unplugged. Multi V = Outdoor
unit coil sensor. Text 45 for diagnostics
49
Check power supply voltage to the outdoor unit
is correct (1ph ?220 Vac ±10% or 3ph ?380 Vac ±10%). If OK check fuses, if
fuses OK, replace outdoor main
PCB
PCB
50
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
51
Unit
mismatch. Check model number of units do not exceed maximum. Multi V - also
check Sub outdoor unit dipswitch settings
52
Communication error between inverter PCB and
main outdoor unit PCB. Check wiring fuses and LEDs . If OK either inverter or
main PCB defective.
53
Comms
error indoor to outdoor unit. Check your wiring . Split and Multi - check
voltage from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4
54
Reverse
or open phase. Check all 3 phases are present and correct. If correct voltage
appears at all three phases, swap any two to cure the fault
55
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
56
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
57
Comms error between outdoor main PCB and
inverter PCB. Check wiring fuses and LEDs are lit. If OK either inverter or
main PCB defective
58
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
59
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
60
Outdoor unit PCB EEPROM failure, try removing
EEPROM and refitting if removable (possible contact fault), otherwise replace
PCB if the EEPROM is nonremovable.
61
Condenser coil over 65°C. Check coil and filters
are clean and free from debris, and airflow is OK. Check system pressures for
non-condesables
62
Inverter over 85°C. Check air flow across heat
sink, check inverter tight to heatsink use thermal paste. Multi V - check
inverter cooling fan
63
Multi F(DX) - "Cond. Pipe Sensor Temp.
Low" (opposite to Error Code 61). Check Temperature/Resistance reading and
replace sensor if found to be faulty. If
sensor okay, check for cause of low temperature and rectify.
sensor okay, check for cause of low temperature and rectify.
64
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
65
Outdoor unit inverter fin temperature sensor
fault. Disconnect from PCB measure resistance. 8 kOhm at 30°C and 13 kOhm at
20°C
67
Outdoor
Fan Motor siezed, or rotation sensing circuit failure. Check motor for
mechanical and/or electrical failure, if okay replace pcb.
100
Excessive
discharge temperature rise 105°C Sub condenser 1 standard compressor. Check
refrigerant
101
Excessive
discharge temperature rise 105°C Sub condenser 1 standard compressor. Check
refrigerant
102
Excessive discharge temperature rise 105°C Sub
condenser 2 standard compressor. Check refrigerant
103
Excessive discharge temperature rise 105°C Sub
condenser 2 standard compressor. Check refrigerant
104
Communication error between Main and Sub outdoor
units. Check comms wiring and power to all outdoor units
105
Communication error between outdoor main PCB and
fan PCB. Check plug connections and LEDs. If OK, replace either main or fan PCB
106
Outdoor
unit fan motor high current. Check fans rotate freely, and are connected
correctly
107
Outdoor unit low voltage to fan PCB. Check 300
Vdc supply, check fuses and plug connections. If OK, replace fan PCB
108
Communication
error between outdoor main PCB, and fan PCB. Check plug connections and LEDs.
If OK replace either main or fan PCB
109
Sub 1
excessive rise of high pressure. Check pressures, check for non condensables,
check heat exchanger coil is free from debris
110
Sub 1
reverse or open phase. Check all 3 phases are present and correct. If correct
voltage appears at all three phases, swap any two to cure the fault
111
Communication
error between Main and Sub outdoor units. Check comms wiring and power to all
outdoor units
113
Main
outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
114
Main
outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
115
Main
outdoor unit Subcool outlet sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
116
Sub 1 high pressure sensor fault. Check dc
voltage between white and black cable on plug. Multi V: 1 Vdc = 8 bar up to 2.5
Vdc = 37 bar
117
Sub 1 low
pressure sensor fault. Check dc voltage between white and black cable on plug.
Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar
118
Sub 1
outdoor unit air sensor fault. Disconnect from PCB and measure resistance. 8
kOhm at 30°C and 13 kOhm at 20°C. If OK replace PCB, if not replace sensor
120
Sub 1
outdoor unit suction sensor fault. Disconnect from PCB and measure resistance.
10 kOhm at 10°C and 4 kOhm at 30°C. if not replace sensor
121
Sub 1 compressor 1 discharge sensor fault.
Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C.
if not replace sensor
122
Sub 1
compressor 2 discharge sensor fault. Disconnect from PCB measure resistance 237
kOhm at 20°C and 168 kOhm at 30°C. if not replace sensor
123
Sub 1
outdoor unit coil sensor A fault. Disconnect from PCB measure resistance. 10
kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor
124
Sub 1
outdoor unit coil sensor B fault. Disconnect from PCB measure resistance. 10
kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor
125
Sub 1
outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
126
Sub 1
outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
127
Sub 1 outdoor unit Subcool outlet sensor fault.
Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
128
Sub 2
high pressure sensor fault. Check dc voltage between white and black cable on
plug. Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar
129
Sub 2 low pressure sensor fault. Check dc
voltage between white and black cable on plug. Multi V: 1 Vdc = 4 bar up to 5
Vdc = 32 bar
130
Sub 2 outdoor unit air sensor fault. Disconnect
from PCB and measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C. If OK
replace PCB, if not replace sensor
132
Sub 2 outdoor unit suction sensor fault.
Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at
30°C.if not replace sensor
133
Sub 2
compressor 1 discharge sensor fault. Disconnect from PCB measure resistance 237
kOhm at 20°C and 168kOhm at 30°C. if not replace sensor
134
Sub 2
compressor 2 discharge sensor fault. Disconnect from PCB measure resistance 237
kOhm at 20°C and 168kOhm at 30°C.if not replace sensor
135
Sub 2
outdoor unit coil sensor A fault. Disconnect from PCB measure resistance. 10
kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor
136
Sub 2 outdoor unit coil sensor B fault.
Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If
OK replace PCB, if not replace sensor
137
Sub 2
outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
138
Sub 2
outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
139
Sub 2
outdoor unit Subcool outlet sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
140
Sub 2
excessive rise of high pressure. Check pressures, check for non condensables,
check heat exchanger coil is free from debris
141
Sub 2 reverse or open phase. Check all 3 phases
are present and correct. If correct voltage appears at all three phases, swap
any two to cure the fault
142
Communication
error between Main and Sub outdoor units. Check comms wiring and power to all
outdoor units
143
Sub 1
excessive rise of high pressure. Check pressures, check for non condensables,
check heat exchanger coil is free from debris
144
Sub 1 excessive drop of low pressure. Check
pressures, check for non condensables, check heat exchanger coil is free from
debris
145
Sub 2
excessive rise of high pressure. Check pressures, check for non condensables,
check heat exchanger coil is free from debris
146
Sub 2 excessive drop of low pressure. Check
pressures, check for non condensables, check heat exchanger coil is free from
debris
147
Sub 1
check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or
3ph 380 Vac ±10%).check fuses, if fuses OK replace outdoor main PCB
148
Sub 1 check power supply voltage to the outdoor
unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses
OK replace outdoor main PCB
149
Sub 2
check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or
3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB
150
Sub 2
check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or
3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB
151
Faulty 4 way valve. Check solenoid coil and
output from PCB. If OK, mechanical failure.
152
Excessive
discharge temperature rise 105°C Sub condenser 2 standard compressor. Check
refrigerant
153
Excessive
discharge temperature rise 105°C Sub condenser 2 standard compressor. Check
refrigerant
154
Sub 3 excessive rise of high pressure. Check
pressures, check for non condensables, check heat exchanger coil is free from
debris
155
Sub 3
reverse or open phase. Check all 3 phases are present and correct. If correct
voltage appears at all three phases, swap any two to cure the fault
156
Communication error between Main and Sub outdoor
units. Check comms wiring and power to all outdoor units
157
Sub 3
high pressure sensor fault. Check dc voltage between white and black cable on
plug. Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar
158
Sub 3 low
pressure sensor fault. Check dc voltage between white and black cable on plug.
Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar
LG AIR CONDITIONER
ERROR CODES AND DESCRIPTION
159
Sub 3 outdoor unit air sensor fault. Disconnect
from PCB and measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C. If OK
replace PCB, if not replace sensor
161
Sub 3
outdoor unit suction sensor fault. Disconnect from PCB and measure resistance.
10 kOhm at 10°C and 4 kOhm at 30°C. if not replace sensor
162
Sub 3 compressor 1 discharge sensor fault.
Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C.
if not replace sensor
163
Sub 3 compressor 2 discharge sensor fault.
Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C.if
not replace sensor
164
Sub 3 outdoor unit coil sensor A fault.
Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If
OK replace PCB, if not replace sensor
165
Sub 3
outdoor unit coil sensor B fault. Disconnect from PCB measure resistance. 10
kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor
166
Sub 3
outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
167
Sub 3
outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
168
Sub 3
outdoor unit Subcool outlet sensor fault. Disconnect from PCB and measure
resistance. 10 kOhm at 10°C and 4 kOhm at 30°C
169
Sub 3
excessive rise of high pressure. Check pressures, check for non condensables,
check heat exchanger coil is free from debris
170
Sub 3
excessive drop of low pressure. Check pressures, check for non condensables,
check heat exchanger coil is free from debris
171
Sub 3
check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or
3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB
172
Sub 3 check power supply voltage to the outdoor
unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses
OK replace outdoor main PCB
173
Main
outdoor unit standard compressor not starting. Check output from main PCB,
check contactor, and check wiring connections. If OK compressor faulty
174
Sub 1
standard compressor 1 not starting. Check output from main PCB, check
contactor, and check wiring connections. If OK compressor faulty
175
Sub 1
standard compressor 2 not starting. Check output from main PCB, check
contactor, and check wiring connections. If OK compressor faulty
176
Sub 2 standard compressor 1 not starting. Check
output from main PCB, check contactor, and check wiring connections. If OK
compressor faulty
177
Sub 2
standard compressor 2 not starting. Check output from main PCB, check
contactor, and check wiring connections. If OK compressor faulty
204
Comms
Error between Outdoor Unit and HR Box No1. 1. Defective connection in HR unit
power supply and transmission connection 2. Wrong setting of the HR
unit Rotary switch and Dip switch 3. Defective HR unit PCB
unit Rotary switch and Dip switch 3. Defective HR unit PCB
208
Comms
Error between Outdoor Unit and HR Box No2. 1. Defective connection in HR unit
power supply and transmission connection 2. Wrong setting of the HR unit Rotary switch and Dip switch 3. Defective HR unit PCB
212
Comms
Error between Outdoor Unit and HR Box No3. 1. Defective connection in HR unit
power supply and transmission connection 2. Wrong setting of the HR
unit Rotary switch and Dip switch 3. Defective HR unit PCB
unit Rotary switch and Dip switch 3. Defective HR unit PCB
240
Central controller
wiring error. Check all comms wiring, including between controller and CNU, and
IP addresses. If OK possible defective CNU
241
Central controller data sending error. Either
defective CNU or Central controller initialisation failure
242
Central
controller data receiving error. Either defective CNU or Central controller
initialisation failure
243
Central
controller. Comms cable too long or picking up external electrical noise. If
OK, mismatching of controllers, or defective CNU
244
Central
controller data receiving time out. Either defective CNU or Central controller
initialisation failure
245
Central
controller data sending time out. Either defective CNU or Central controller
initialisation failure
246
Central
controller data receiving time out. Either defective CNU or Central controller
initialisation failure
250
Central
controller data receiving error. Either comms cable picking up external
electrical noise, or defective CNU
251
Central
controller receiving no data. Either comms cable picking up external electrical
noise, or defective CNU
252
Central
controller incorrect address error. Check addresses match, if OK either comms
cable picking up external electrical noise, or defective CNU
253
Central
Controller Disconnection Error, No response from Air Conditioner. Check wiring,
if OK either comms cable picking up external electrical noise, defective CNU,
or Interface.
C1
C1
Indoor unit return air sensor fault, Open or
Short. Disconnect sensor from PCB and measure resistance. 8 kOhm at 30C and 13
kOhm at 20C if not replace
sensor
sensor
C2
Indoor
Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB
and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5
kOhm at 25C. If not replace sensor.
kOhm at 25C. If not replace sensor.
C4
RAC
Product
= Heat Sink Sensor Error, Open/Short Cct or over 95C. Commercial
Product = Condensate pump float switch risen. Check drain pan is
empty, check pump is working OK. If no pump check blue jumper plug is
inserted in
socket CN Float.
C5
Comms
Error, check your wiring, remove external pumps. Split/Multi - check volts from
terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4
C6
Inverter compressor run current high. Check
compressor windings all equal 1 to 4 Ohms, Check to earth 50 MOhm minimum,
check run current
C7
Splits =
Compressor Over Current (CT2), also see Code 06.
C8
RAC Indoor unit BLDC Fan problem. This is caused
by the Indoor fan being locked. Check fan motor is plugged in correctly,
Electrically & Mechanically sound. Check the fan motor turns freely, check the AC Voltage supplied to the fan
motor, this will vary from 120 V ac at low speed to 170V AC at high speed. If
no Voltage is present the the PCB is faulty, if Voltage is present the fan motor
will be Faulty.
C9
Outdoor unit fan problem. Check Outdoor fan
motor is plugged in, Electrically & Mechanically sound, if not replace
motor, otherwise replace PCB.
CA
Compressor
discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at
20°C, 168 kOhm at 30C.
CC
RAC
Product = EEPROM Sum Check Error, text 60 for help.
Cd
RAC Product = PSC (Reactor) Error, text 27 for
help.
CE
RAC
Product = Compressor Phase Current Error
CH00
Text the
1, 2 or 3 digit fault code number only. I.e. If you see fault code CH07 on your
indoor unit or R/Controller, only type 7 or 07 in your text message.
CH01
Indoor
unit return air sensor fault. Disconnect sensor from PCB and measure
resistance. 8 kOhm at 30C and 13 kOhm at 20C if not replace sensor
CH02
Indoor Pipe Sensor or Outdoor Sensor Assy fault,
Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm
at 25C, Pipe sensor = 5 kOhm at 25C. If not replace sensor.
CH03
Remote
controller comms error. Check wired correctly, if so check dipswitch in RC. Set
to Sg for 1 unit, or Gr for group then reset power
CH04
RAC Product = Heat Sink Sensor Error, Open/Short
Cct or over 95C. Commercial Product = Condensate pump float switch risen. Check
drain pan is empty, check pump is working OK. If no pump check blue jumper plug
is inserted in socket CN Float.
CH05
Comms
Error, check your wiring, remove external pumps. Split/Multi - check volts from
terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4
CH06
Indoor
unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10C
and 4 kOhm at 30C. if not replace sensor. Split = text 21
CH07
Multi
Splits and Multi V = indoor unit is set to run in a different mode from the
master indoor unit. Set ALL indoor units to cooling or ALL to heating to clear.
Splits = Compressor Over Current (CT2), also see Code 06.
Splits = Compressor Over Current (CT2), also see Code 06.
CH08
RAC Indoor unit BLDC Fan problem. This is caused
by the Indoor fan being locked. Check fan motor is plugged in correctly, Electrically
& Mechanically sound. Check the fan motor turns freely, check the AC
Voltage supplied to the fan motor, this will vary from 120 V ac at low speed to
170V AC at high speed. If no Voltage is present the the PCB is faulty, if
Voltage is present the fan motor will be Faulty.
CH09
Split =
Outdoor unit fan problem. Check Outdoor fan motor is plugged in, Electrically
& Mechanically sound, if not replace motor, otherwise replace PCB. Multi V =
indoor PCB failure. Replace PCB
CH10
RAC
Product: Compressor discharge sensor fault. Disconnect from PCB measure
resistance 237 kOhm at 20°C, 168 kOhm at 30C. Multi Fdx & Multi V text 8
CH11
Multi V
indoor unit not connected to an outdoor unit. Check comms wiring is correct,
and check initialisation has been carried out correctly
CH12
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH13
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH14
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH15
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
CH16
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH17
no such fault code Text 1, 2 or 3 digit fault
code number only. If you see fault code CH07 only type 7 in your text message
CH18
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH19
no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message
CH19
no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message
CH20
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07
only type 7 in your text message
CH21
Inverter
compressor run current high. Check compressor windings all equal 1 to 4
OhmsCheck to earth 50 MOhm minimum, check run current
CH22
Inverter compressor run current high. Check
compressor windings all equal 1 to 4 Ohms . Check to earth 50 MOhm minimum,
check run current
CH23
Inverter dc voltage low. Check dc voltage of
capacitors 300 Vdc for 1Ph and 600 Vdc for 3Ph. If OK change outdoor inverter
PCB
CH24
Splits
and Multi Splits = High or low pressure trip. Low at 1 bar High at 35 bar check
pressures. Multi V = High pressure trip.
CH25
Check
power supply voltage to the outdoor unit is correct (1ph ?220 Vac ±10% or 3ph
?380 Vac ±10%). If OK, check fuses, if fuses are OK replace outdoor
main PCB
main PCB
CH26
Inverter
compressor seized. Check compressor windings all equal resistance 1 to 4 Ohms,
check to earth 50 MOhm minimum, check run current and Inverter outputs
CH27
Inverter current irregularity. Check inverter
PCB and reactor
CH28
Inverter
dc voltage too high. Check dc voltage of capacitors 300 Vdc for 1Ph and 600 Vdc
for 3Ph. If OK change outdoor inverter PCB
CH29
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH30
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH31
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH32
Inverter compressor discharge temperature too
high. If over 105°C, check refrigerant charge
CH33
Excessive
rise of standard compressor discharge temperature. If over 105°C check
refrigerant charge
CH34
Excessive
high pressure rise, over 35 bar at HP sensor. Check pressures, check coils, and
filters are clean check for OFN in system pipework
CH35
Excessive
low pressure drop under 1 Bar at LP sensor. Check pressures, and check service
valves open
CH36
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH37
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH38
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH39
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH40
Inverter
ac current abnormal. Check compressor windings all equal resistance 1 to 4
Ohms, check to earth 50 MOhm minimum, check run current and inverter outputs
CH41
Inverter
compressor discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm
at 20C and 168 kOhm at 30C.
CH42
Low
pressure sensor fault. Check dc voltage between white and black cable on plug.
Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar CH43 High pressure sensor fault.
Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 8 bar
up to 2.5 Vdc = 37 bar
CH44
Outdoor
unit air sensor fault. Disconnect from PCB and measure resistance. 8 kOhm at
30°C and 13 kOhm at 20°C. If OK replace PCB, if not replace sensor
CH45
Outdoor
unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C
and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor
CH46
Outdoor
unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm
at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor
CH47
Compressor
discharge sensor fault. Disconnect from PCB measure resistance. 237 kOhm at
20°C and 168 kOhm at 30°C. If OK replace PCB, if not replace
sensor
sensor
CH48
Split/Multi
Split = Outdoor unit discharge and air sensor both unplugged. Multi V = Outdoor
unit coil sensor. Text 45 for diagnostics
CH49
Check
power supply voltage to the outdoor unit is correct (1ph ?220 Vac ±10% or 3ph
?380 Vac ±10%). If OK check fuses, if fuses OK, replace outdoor main PCB
CH50
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH51
Unit
mismatch. Check model number of units do not exceed maximum. Multi V - also
check Sub outdoor unit dipswitch settings
CH52
Communication
error between inverter PCB and main outdoor unit PCB. Check wiring fuses and
LEDs . If OK either inverter or main PCB defective
CH53
Comms error indoor to outdoor unit. Check your
wiring . Split and Multi - check voltage from terminal N to 3 = 0 - 65 Vdc,
Multi V - 4 Vdc terminals 3 and 4
CH54
Reverse
or open phase. Check all 3 phases are present and correct. If correct voltage
appears at all three phases, swap any two to cure the fault
CH55
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH56
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH57
Comms error between outdoor main PCB and inverter PCB. Check wiring fuses
and LEDs are lit. If OK either inverter or main PCB defective
CH58
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH59
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH60
Outdoor
unit PCB EEPROM failure, try removing EEPROM and refitting if removable
(possible contact fault), otherwise replace PCB if the EEPROM is nonremovable.
CH61
Condenser
coil over 65°C. Check coil and filters are clean and free from debris, and
airflow is OK. Check system pressures for non-condesables
CH62
Inverter
over 85°C. Check air flow across heat sink, check inverter tight to heatsink
use thermal paste. Multi V - check inverter cooling fan
CH63
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH64
no such
fault code Text 1, 2 or 3 digit fault code number only. If you see fault code
CH07 only type 7 in your text message
CH65
Outdoor
unit inverter fin temperature sensor fault. Disconnect from PCB measure
resistance. 8 kOhm at 30°C and 13 kOhm at 20°C
CH67
Outdoor
Fan Motor siezed, or rotation sensing circuit failure. Check motor for
mechanical and electrical failure.
CL
CL = Child Lock. Press Timer & Min buttons simultaneously for 5 seconds
to engage/disengage function. help Text the 1, 2 or 3 digit fault code number only. I.e. If you see fault
code CH07 on your indoor unit or R/Controller, only type 7 or 07 in your text
message.
HL
Condensate pump float switch risen. Check drain
pan is empty, check pump is working OK. If no pump check blue jumper plug is
inserted in socket CN Float.
Alternatively, Dry Contact Interface is in "OFF" condition. Check status and adjust as necessary.
Alternatively, Dry Contact Interface is in "OFF" condition. Check status and adjust as necessary.
Po
Po = Jet
Cool Mode selected. To cancel press Jet Cool, Fan Speed or Set Temperature
button.