Akira Air Conditioner – Gas charging procedure – AC S10CK - S10HK
AIR PURGING (INSTALLATION)Required tools: hexagonal wrench, adjustable wrench, torque wrenches, wrench to hold the joints, and gas leak detector.
The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and gas leaks, a gas cylinder and the charge set will be needed.
The air in the indoor unit and in the piping must be purged. If air remains in the refrigerant pipes, it will affect the compressor, reduce the cooling and heating capacity, and could lead to a malfunction.
Be sure to use a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.
Caution: Do not leak the gas in the air during air purging.
> Recheck the piping connections.
> Open the valve spindle of the 2-way valve counter-clockwise proximately 90°,wait 10 seconds, and then set it to closed position. Be sure to use a hexagonal wrench to operate the spindle.
> Check the flare connections for refrigerant gas leakage.
> Purge the air from the system. Set the 2-way valve to the open position and remove the cap from the 3-way valve’s service port. Using the hexagonal wrench to press the valve core pin, discharge for three seconds and then wait for one minute. Repeat this three times.
> Use torque wrench to tighten the service port cap to a torque of 1.8kg.cm.
> Set the 3-way valve to the back seat.
> Mount the valve caps to the 2-way and 3-way valves.
> Check for gas leakage. At this time, especially check for gas leakage from the 2-way and 3-way valve’s caps, and from the service port cap.
Caution: If gas leakage is discovered, take the following measures.
>If the gas leakage stops when the piping connections are tightened further, continue working.
> If the gas leakage does not stop when the piping connections are tightened, repair the location of the leakage, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.
PUMPING DOWN (BEFORE RE-INSTALLATION)
Confirm that both the 2-way and 3-way valves are set to the open position.
> Remove the valve caps and confirm that the valve spindles are in the open position.
> Be sure to use a hexagonal wrench to operate the valve spindle.
Operate the unit for 10~15 minutes.
Stop operation and wait for 3 minutes, then connect the charge set to the service port of the3-way valve.
> Connect the charge hose with the push pin to the service port.
Air purging of the charge hose
> Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
Set the 2-way valve to the closed position.
Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2.g.
Immediately set the 3-way valve to the
closed position.
> Do this quickly so that the gauge ends up indicating 3 to 5kg/cm2.g.
Disconnect the charge set, and amount the 2-way and 3-way valve’s caps and the service port cap.
> Use torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
> Be sure to check for gas leakage.
RE-AIR PURGING FOR RE-INSTALLATION> Do this quickly so that the gauge ends up indicating 3 to 5kg/cm2.g.
Disconnect the charge set, and amount the 2-way and 3-way valve’s caps and the service port cap.
> Use torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
> Be sure to check for gas leakage.
Confirm that both the 2-way valve and
the 3-way valve are set to the closed position.
Connect the charge set and a gas cylinder to the service port of the 3-way valve.
> Leave the valve on the gas cylinder closed.
Air purging
> Open the valves on the gas cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45°for 3 seconds, then closing it for 1 minute. Repeat 3 times.
> After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
Connect the charge set and a gas cylinder to the service port of the 3-way valve.
> Leave the valve on the gas cylinder closed.
Air purging
> Open the valves on the gas cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45°for 3 seconds, then closing it for 1 minute. Repeat 3 times.
> After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
Check the flare connections for gas
leakage.
Disconnect the charge set and the gas cylinder, and set the 2-way and 3-way valves to the open position.
> Be sure to use a hexagonal wrench to operate the valve spindles.
Mount the valve caps and the service port cap.
> Use torque wrench to tighten the service port cap to a torque of 1.8kg.m.
> Be sure to check for gas leakage.
Caution: Do not leak the gas in the air during air purging.
Disconnect the charge set and the gas cylinder, and set the 2-way and 3-way valves to the open position.
> Be sure to use a hexagonal wrench to operate the valve spindles.
Mount the valve caps and the service port cap.
> Use torque wrench to tighten the service port cap to a torque of 1.8kg.m.
> Be sure to check for gas leakage.
Caution: Do not leak the gas in the air during air purging.
BALANCE REFRIGERANT OF THE 2-WAY, 3-WAY VALVES (GAS LEAKED)
Confirm that both the 2-way and 3-way valves are set to the back seat.
Connect the charge set to the 3-way valve’s service port.
Confirm that both the 2-way and 3-way valves are set to the back seat.
Connect the charge set to the 3-way valve’s service port.
>Leave the valve on the charge set
closed.
> Connect the charge hose with the push pin to the service port.
> Connect the charge hose with the push pin to the service port.
Open the valve (Low side)on the charge
set and discharged the refrigerant until the gauge indicates 0kg/cm2.g.
> If there is no air in the refrigerant cycle (the pressure when the air conditioner is not running is higher than 1 kg/cm2.g),discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm2.g.If this is the case, it will not be necessary to apply an evacuation.
> Discharge the refrigerant gradually. If it is discharged too suddenly, the refrigeration oil will also be discharged.
> If there is no air in the refrigerant cycle (the pressure when the air conditioner is not running is higher than 1 kg/cm2.g),discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm2.g.If this is the case, it will not be necessary to apply an evacuation.
> Discharge the refrigerant gradually. If it is discharged too suddenly, the refrigeration oil will also be discharged.
EVACUATION (ALL AMOUNT OF REFRIGERANT LEAKED)
Connect the vacuum pump to the charge set’s center hose.
Evacuating for approximately one hour.
> Confirm that the gauge needle has moved toward -76cmHg (vacuum of 4 mmHg or less)
Connect the vacuum pump to the charge set’s center hose.
Evacuating for approximately one hour.
> Confirm that the gauge needle has moved toward -76cmHg (vacuum of 4 mmHg or less)
Close the valve (Low side) on the
charge set, turn off the vacuum pump, and confirm that the gauge needle does
not move (approximately 5 minutes after turning off the vacuum pump).
Disconnect the charge hose from the vacuum pump.
> If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Disconnect the charge hose from the vacuum pump.
> If the vacuum pump oil becomes dirty or depleted, replenish as needed.
GAS CHARGING (AFTER EVACUATION)
Connect the charge hose to the charging cylinder.
> Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
> If you are using a gas cylinder ,also use a scale and level the cylinder so that the system can be charged with liquid.
Purge the air from the charge hose.
>
Open the valve at the bottom of the cylinder and press the check valve
on the charge set to purge the air.(Be careful of the liquid
refrigerant).The procedure is the same if using a gas cylinder.
Open the valve (Low side on the charge set) and charge the system with liquid refrigerant.
>
If the system can not be charged with the specified amount of
refrigerant, it can be charged with a little at a time (approximately
150g each time) while operating the air conditioner in the cooling
cycle. However, one time is not sufficient, wait approximately 1 minute
and then repeat the procedure (pumping down pin).
>
This is different from previous procedures. Because you are charging
with liquid refrigerant from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant while operating the air
conditioner.
Immediately disconnect the charge hose from the 3-way valve’s service port.
> Stopping partway will allow the gas to be discharged.
> If the system has been charged with liquid refrigerant while operating the air conditioner before disconnecting the hose.
Mount the valve caps and service port cap.
> Use torque wrench to tighten the service port cap to a torque of 1.8kg.m.
> Be sure to check for gas leakage.